Portable Fire Monitor

ES0304-PM

Maximum Flow: 1250 GPM @ 145 PSI (4800 L/min @ 10Bar)

Eurosafe Brand ES0304-PM Portable Fire Monitor is suitable various application due to the Flexible which could carry by one man to different areas quickly. ES0304-PM is good quality with competitive cost, highly welcome among customer.

Eurosafe ES0304 PM Portable Fire Monitor series INDIVIDUAL POST PAGE

FEATURES

ES0304 PM Portable Fire Monitor series 1 1
ES0304 PM Portable Fire Monitor series 2

Specification

ES0304-PM Technical Specifications
ModelES0304-PMMaterial
Flow Rate2400-4800LPM (Automatic Nozzle)

Body: Hard Anodized Aluminum alloy

Nozzle: Hard Anodized Aluminum alloy

Folding leg: Stainless Steel

Spikes: Stainless Steel

Working Pressure1.0 MPa
Water Jetting Range≥ 80 meters
Working AngleHorizontal 360°; 0°to +90° elevate vertically
Outlet2.5” NH Connection
Inlet2 Inlets, 2.5”, All International Coupling available

Danger !

Operating & Brief InSTRUCTIONS

INSTALLING THE MONITOR TOP ON THE BASE

To install the monitor on portable base:

  1. Turn elevation handwheel to make sure the elevation of the nozzle is above the 35° safety stop. Verify that the elevation stop pin is down and engaged.
  2. Make sure the slide bar is in the up position.
  3. Holding the monitor by the top carrying handle, position monitor over base and slide straight down.
  4. Push the slide bar down and watch the pawls engage the groove in the base and the safety plunger engage in the hole in the slide bar.
ES0304 PM Portable Fire Monitor series 1
ES0304 PM Portable Fire Monitor series 3

Hold monitor over base and lower straight down. Push Slide Bar DOWN to engage the plunger and pawls.

ES0304 PM Portable Fire Monitor series 4

Slide Bar in the UP position.

POSITIONING STREAM - HORIZONTAL ROTATION AND LOCK

The monitor can be rotated horizontally on the base to a desired position. The rotational position of the monitor must be locked before flowing water. When not rotating the monitor on the base, keep the rotation locked.

To position the monitor horizontally:

  1. Stop all water flow to the monitor.
  2. Depress the safety plunger to disengage the spring-loaded pawls from the groove in the base.
  3. Holding the monitor by the top carrying handle, lift the monitor straight up off the base
ES0304 PM Portable Fire Monitor series 6

Locked.

REMOVE THE MONITOR TOP ON THE BASE

To remove the monitor top from the truck mount flange or portable base:

  1. With the monitor on the base, rotate the monitor to a desired position.
  2. Lock the rotational position by moving the rotation lock lever to the down position.
  3. Manually unlock the rotational lock by moving the rotation lock lever to the up Position before repositioning or removing the monitor from the base. A small spring holds the lever in the up (unlocked) position.
ES0304 PM Portable Fire Monitor series 7

Unlocked.

WARNING!

POSITIONING STREAM - ELEVATION CONTROL AND STOP PIN

The handwheel controls nozzle elevation.

  1. -Clockwise rotation of the wheel will raise the nozzle.
  2. -Counter-clockwise rotation of the wheel will lower the nozzle.

When mounted on a truck base, the nozzle may be lowered below the 35° safety stop by pulling out the stop pin and rotating the handwheel below the 35° stop. When the nozzle is raised back above 35°, the spring loaded stop pin snaps back into position, automatically limiting the elevation of the nozzle with respect to the base to 35°.

ES0304 PM Portable Fire Monitor series 8

WARNING!

ES0304 PM Portable Fire Monitor series 9

Elevation Handwheel Control

ES0304 PM Portable Fire Monitor series 10

Elevation Pin Stop

Folding Operation

The portable base legs are extended by following these steps:

  1. Hold the base carrying handle with one hand and grasp the end of one of the longer legs with the other hand.
  2. Pull this leg away from the base forward in an arc, until the locking pin engages. The locking pin is spring loaded and automatically engages when the legs are in the correct position. Watch the leg lock knob drop down even with the lower band on the base, indicated by an arrow.
  3. Repeat steps 1 & 2 for the other set of legs.
  4. Set portable base on even ground with all leg spikes in contact with the ground.
  5. Lift the storage cap to remove the anchor strap stored inside the base. Keep the strap near the monitor as it will be used to tie off the monitor before use.

To retract the legs for carrying or storage:

The handwheel controls nozzle elevation.

  1. Pull up on one of the spring loaded leg lock knobs to disengage.
  2. Grasp the forward leg on the same side as the knob and push it in an arc, towards the rear of the unit. The leg lock knob may be released as soon as the front leg begins to move out of position.
  3. Continue to push until both legs come in contact with the rear stop.
  4. Repeat steps 1, 2, & 3 for the other set of legs.

When mounted on a truck base, the nozzle may be lowered below the 35° safety stop by pulling out the stop pin and rotating the handwheel below the 35° stop. When the nozzle is raised back above 35°, the spring loaded stop pin snaps back into position, automatically limiting the elevation of the nozzle with respect to the base to 35°.

ES0304 PM Portable Fire Monitor series 11

WARNING!

AUTOMATIC, CONSTANT, SELECTABLE FLOW NOZZLES

The EUROSAFE ES0304-PM Portable Monitor could attached a variety of water/ water & foam nozzle.
This instruction main for Automatic flow nozzle, if you have special requirements, Please view our website to contact our sales team for more info – www.eurosafeglobal.com

AUTOMATIC, CONSTANT, SELECTABLE FLOW NOZZLES

MAINTENANCE

The maintenance of fire monitors should be handled by dedicated personnel.

ORDERING GUIDE