Pre-Pack Integrated

Pre-Action System

UL Listed, Model: ES0201

DESCRIPTION

EUROSAFE Pre-Pack is a pre-assembled Pre-Action System enclosed in cabinet. Pre-action systems are designed for water sensitive areas that require protection from inadvertent water flow into the sprinkler system piping. Eurosafe Pre-Pack system comes with grooved ends to provide minimum installation time. It comes in a compact, space saving, self-standing cabinet while providing an aesthetically pleasing appearance.

Features

14 Eurosafe Preaction Systems

Technical Data

Specification Details
Size 50, 80, 100, 150 & 200 NB
Deluge Valve Model ES0201, UL Listed
Riser Check Valve Model CH
Water Motor Gong Bell UL Listed (Optional supply)
Maximum Working Pressure 17.5 kg/sq.cm (250 psi)
System End Connection Grooved – Standard supply Flanged – Optional supply
Release Panel POTTER, UL Listed (Optional)
Water Flow Switch POTTER, UL Listed
Low Pressure Alarm Switch POTTER, UL Listed
Solenoid Valve Normally closed, 24 VDC, UL Listed
Manual System Shut Off Valve Butterfly Valve, UL Listed (With Tamper Switch)
Automatic Air Supply Oil Less Riser Mounted Compressor (Optional)
Type Single Interlock – Wet Pilot Single Interlock – Dry Pilot Single Interlock – Electric Double Interlock – Electric/Pneumatic Double Interlock – Electric/Electric
Cabinet 14 SWG, Red Finish (RAL 3001)
Approval UL Listed

CONSTRUCTION

Pre-Pack is a pre-assembled Pre-Action System enclosed in free standing cabinet. The cabinet is pre-wired and requires water inlet, outlet valve riser and drain. All connections are grooved-type to provide minimal installation time.

Pre-Pack includes Deluge Valve, Riser Check Valve, Water Supply Stop Valve, Water Flow Supervisory Switch, Pressure Gauges, Built-in Air Compressor and Control Panel with battery backup. The cabinet comes with windows for viewing the release panel function and pressure gauges.

The cabinet is constructed of 14 gauge steel and standard finish is red. The front door is hinged and removable. All four sides of the cabinet can be removed for ease of maintenance. Cabinet base plate comes with pre-drilled holes, which provide an anchor point for the cabinet for securing to the floor. All internal valves and major components are individually tagged for identification.

The water motor gong bell is supplied pre-assembled with inlet & drain connection to the left side of the cabinet. If required, the water motor gong bell can be supplied loose and a connection is provided for field installation. A hard piped funnel drain is connected through swing check valve to the main drain line. The funnel is provided with splash proof cap so that water does not splash into the cabinet during flow. It is fail-safe feature allowing water to overflow in the event the drain is blocked. A cable entry is provided at bottom of the cabinet. Pre-Pack is also available without Releasing/ Control Panel and Air Compressor. Optionally a Nitrogen Generator System can be connected to EUROSAFE Pre-Pack System.

OPERATION

System comprises mainly of two configurations:

1. Double Interlock

Double Interlock configuration is more commonly used in industry and it comes with two options:

Both these options have been specified in individual datasheets.

2. Single Interlock

Single Interlock configuration comes in three options:

Double Interlock Pre-Action System with Electric/Pneumatic Actuation:

This is most commonly used system. This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check, so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 42 psi (2.94 bar). A supervisory low pressure alarm switch can be set at 20 psi (1.40 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.

The releasing trim for Deluge Valve utilizes a Solenoid Valve and a Dry Pilot Actuator in a series configuration. The system air pressure holds the Dry Pilot Actuator closed, whereas the Solenoid Valve remains closed until it is electrically energized by a Deluge Valve Releasing Panel (automatic control unit). The Releasing Panel is operated by either a fire detection device or manual electric pull station. In order for the Double Interlock Pre-Action System to automatically actuate, two independent events must occur. The Deluge Valve Releasing Panel must operate and open the Solenoid Valve upon automatic operation of the electric fire detection initiating circuit and the sprinkler system piping must lose air pressure due to operation of one or more sprinklers. The Double Interlock Pre-Action System will automatically actuate only when both the Dry Pilot Actuator and the Solenoid Valve are open at the same time. Unintended opening of just the Dry Pilot Actuator or the Solenoid Valve will only cause an alarm and not actuate the system or flood the sprinkler system piping.

Double Interlock Pre-Action System with Electric/Pneumatic Actuation:

This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
The releasing trim for the Deluge Valve utilizes a Solenoid Valve that is energized with cross-zone releasing circuit of release panel.
The Solenoid Valve remains closed until it is electrically energized by a Deluge Valve Releasing Panel (automatic control unit). The Releasing Panel is operated by either a fire detection device or manual electric pull station. In order for the Double Interlock Preaction System to automatically actuate, two independent events must occur. Zone 1 of the Releasing Panel must operate upon automatic operation of the electric fire detection initiating circuit or operation of the electric-manual pull initiating circuit, and Zone 2 of the Releasing Panel must operate via the Low Air Pressure Alarm Switch upon loss of air pressure from the sprinkler system piping, due to operation of one or more sprinklers. The Double Interlock Preaction System will automatically actuate only when both Zone 1 and Zone 2 of the Releasing Panel have operated, energizing the Solenoid Valve.

Single Interlock Pre-Action System with Wet Pilot Actuation

This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
System actuation is carried out by Wet Pilot Line, consisting of Wet Pilot Sprinklers for detection. Actuation of Wet Pilot Line releases Deluge Valve, which allows water to flow into sprinkler line.

Single Interlock Pre-Action System with Dry Pilot Actuation

This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
System actuation is carried out by Dry Pilot Actuator, consisting of Dry Pilot Sprinklers for detection. Actuation of Dry Pilot Actuator releases Deluge Valve, which allows water to flow into sprinkler line. The Dry Pilot Sprinkler line to be pressurized with 42 psi (2.94 bar) air pressure.
Two independent Pressure Maintenance Devices are to be utilized for maintaining the supervisory air pressure and Dry Pilot line pressure.

Single Interlock Pre-Action System with Electric Actuation

This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
System actuation is carried out by supplemental detection system, which typically comprises of 24 VDC heat detectors, smoke detectors, manual pull stations, etc. Actuation of the detection system automatically operates the Deluge Valve, allowing water to flow into the sprinkler piping system, to be discharged from any sprinklers that are open.

INSTALLATION REQUIREMENT

The Pre-Pack Cabinet and all interconnecting piping must be located indoors in a readily visible and accessible location and in an area having minimum temperature of 4oC (40oF). Heat tracing is not permitted. The automatic sprinklers, releasing devices, fire detection devices, must be UL Listed.
Two separate power supply connections to be provided to compressor and electric panel. Two separate terminal sets are provided in the Pre-Pack system.
Electric panel is to be powered by 230V AC, 50 Hz stabilized power supply (with surge protection).
The compressor power requirement is single phase 230V AC, 50 Hz (may vary in different countries) stabilized power supply (with surge protection).

CAUTION!

SYSTEM AIR/NITROGEN PRESSURE REQUIREMENT

A suitable sized water supply to the water supply header, common drain piping, system piping including automatic sprinkler/ nozzles and a detection system piping need to be installed connecting to Pre-Pack .
If the Supervisory Compressor is not taken with PrePack, then a suitable compressor/ plant air supply/N2 connection to be provided with Air Maintenance Device. The selection of compressor shall depend on volume of detection line.

HYDROTESTING

As required by NFPA13, Fire Sprinkler System must be hydrotested and pressure need to be maintained without loss, for two hours. The test pressure shall be as per NFPA 13. In addition to the hydrostatic testing, dry pipe and double interlock pre-action system requires an additional low pressure air test.

INSPECTION AND MAINTENANCE

Inspection and testing is to be carried out only by authorized and trained personnel. DO NOT TURN OFF the water supply or close any valve to make repair(s) or test the valve, without placing a roving fire patrol in the area covered by the system. Also inform the local security personal and central alarm station, so that there is no false alarm signal. It is recommended to carry out physical inspection of the system at least twice a week. The inspection should verify that no damage has taken place to any components and check for following normal condition of the system.
Inspection, Testing and Maintenance must be performed in accordance with NFPA and or authority having jurisdiction.

Note:

The Pressure Gauges standard supply is 300 psi for water gauge for system pressure upto 175 psi. If system pressure is more than 175 psi, then order for 600 psi water pressure gauges.

Double Interlock Pre-Action System with Electric/Pneumatic Actuation:

TYPICAL PRE-PACK ASSEMBLY ARRANGEMENT SYSTEM WITH COMPRESSOR AND RELEASING PANEL

TYPICAL PRE PACK ASSEMBLY ARRANGEMENT SYSTEM WITH COMPRESSOR AND RELEASING PANEL

TYPICAL PRE-PACK ASSEMBLY ARRANGEMENT SYSTEM WITH COMPRESSOR AND RELEASING PANEL

Untitled 1
1BASE FRAME
2CABINET
3BUTTERFLY VALVE WITH TAMPER SWITCH
4DELUGE VALVE
5CHECK VALVE
6PRESSURE GAUGE
7ANTI RESET VALVE
8DRY PILOT ACTUATOR
9EMERGENCY RELEASE STATION
10ANGLE VALVE
11PRIMING VALVE
12RESTRICTED CHECK VALVE
13TRIM FITTINGS
14PRESSURE SWITCH
15SOLENOID VALVE
16SPLASH PROOF FUNNEL
17SPRINKLER ALARM
18RELEASE PANEL
AIR COMPRESSORRESTRICTED CHECK VALVE
20JUNCTION BOX

FRICTION LOSS

Friction loss expressed in equivalent length of Schedule 40 pipe and based on Hazen-Williams Formula with C=120 and a flowing velocity of 4.6 mtrs. (15 ft/sec) is as under. The friction loss is with Deluge Valve, Check Valve, Supply Manifold and System Shutoff Valve.

Valve SizeEquivalent Length in metres
50 mm (2”) BASE FRAME
80 mm (3”) 17.5
100 mm (4”) 20.0
150 mm (6”) 46.2
200 mm (8”) 72.0

GROOVED END DIMENSIONS

 
Valve Size Outer Diameter Groove Diameter Groove Width Outlet face to Groove
50mm (2”) 60mm (2.357”) 57mm (2.250”) 8mm (5/16”) 16mm (5/8”)
80mm (3”) 89mm (3.5”) 85mm (3.344”) 8mm (5/16”) 16mm (5/8”)
100mm (4”) 114mm (4.5”) 110mm (4.334”) 10mm (3/8”) 16mm (5/8”)
150mm (6”) 165mm (6.496”)* 161mm (6.385”) 10mm (3/8”) 16mm (5/8”)
200mm (8”) 219mm (8.625”) 214mm (8.441”) 11mm (7/16”) 19mm (3/4”)

*Pipe diameter 168(6.625”) is optional.

PRINCIPAL COMPONENT

 
No Description Make Approval Datasheet
1 Deluge Valve EUROSAFE UL Listed
2 Check Valve EUROSAFE UL Listed with Pre-action system
3 Single Interlock, Electric Actuation EUROSAFE UL Listed
4 Single Interlock, Dry Pilot Actuation EUROSAFE UL Listed
5 Single Interlock, Wet Pilot Actuation EUROSAFE UL Listed
6 Double Interlock, Electric /Pneumatic Actuation EUROSAFE UL Listed
7 Double Interlock, Electric /Electric Actuation EUROSAFE UL Listed
8 Release Panel Potter UL Listed
9 Pressure Alarm Switch Potter UL Listed
10 Pressure Alarm Switch Potter UL Listed
11 Butterfly Valve (System Shutoff Valve) EUROSAFE UL Listed
12 Automatic Supervisory Air Supply (Compressor) General Air Products CE or UL Listed
13 Air Pressure Maintenance Device EUROSAFE UL Listed with Pre-action System
14 Nitrogen Maintenance Device EUROSAFE

Note:

Battery of 12V-14 Ah is standard supply in separate packing, it needs to be mounted in panel while installing the Pre-Pack . Higher capacity battery is optional supply.

PRE-ACTION CABINET OVERALL DIMENSIONS (WITH COMPRESSOR & RELEASING PANEL)

PRE ACTION CABINET OVERALL DIMENSIONS WITH COMPRESSOR RELEASING PANEL

PRE-ACTION CABINET OVERALL DIMENSIONS (WITHOUT COMPRESSOR & RELEASING PANEL)

PRE ACTION CABINET OVERALL DIMENSIONS WITHOUT COMPRESSOR RELEASING PANEL
Cabinet Dimensions
SIZE A B C D E F G H J K L M M1
50 NB 800 152 248 248 690 407.5 171 185 275 800.5 86 1785 1325
80 NB 800 152 248 248 690 407.5 171 185 275 800.5 86 1785 1325
100 NB 870 90 345 345 730 420 187 185 275 937 86 1895 1400
150 NB 930 80 385 385 750 420 215 190 315 1061 86 2035 1540
200 NB 930 80 385 385 850 476 259 190 340 1170 86 2275 1770