EUROSAFE Pre-Pack is a pre-assembled Pre-Action System enclosed in cabinet. Pre-action systems are designed for water sensitive areas that require protection from inadvertent water flow into the sprinkler system piping. Eurosafe Pre-Pack system comes with grooved ends to provide minimum installation time. It comes in a compact, space saving, self-standing cabinet while providing an aesthetically pleasing appearance.
Specification | Details |
---|---|
Size | 50, 80, 100, 150 & 200 NB |
Deluge Valve | Model ES0201, UL Listed |
Riser Check Valve Model | CH |
Water Motor Gong Bell | UL Listed (Optional supply) |
Maximum Working Pressure | 17.5 kg/sq.cm (250 psi) |
System End Connection | Grooved – Standard supply Flanged – Optional supply |
Release Panel | POTTER, UL Listed (Optional) |
Water Flow Switch | POTTER, UL Listed |
Low Pressure Alarm Switch | POTTER, UL Listed |
Solenoid Valve | Normally closed, 24 VDC, UL Listed |
Manual System Shut Off Valve | Butterfly Valve, UL Listed (With Tamper Switch) |
Automatic Air Supply | Oil Less Riser Mounted Compressor (Optional) |
Type | Single Interlock – Wet Pilot Single Interlock – Dry Pilot Single Interlock – Electric Double Interlock – Electric/Pneumatic Double Interlock – Electric/Electric |
Cabinet | 14 SWG, Red Finish (RAL 3001) |
Approval | UL Listed |
System comprises mainly of two configurations:
Double Interlock configuration is more commonly used in industry and it comes with two options:
Both these options have been specified in individual datasheets.
Single Interlock configuration comes in three options:
This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
The releasing trim for the Deluge Valve utilizes a Solenoid Valve that is energized with cross-zone releasing circuit of release panel.
The Solenoid Valve remains closed until it is electrically energized by a Deluge Valve Releasing Panel (automatic control unit). The Releasing Panel is operated by either a fire detection device or manual electric pull station. In order for the Double Interlock Preaction System to automatically actuate, two independent events must occur. Zone 1 of the Releasing Panel must operate upon automatic operation of the electric fire detection initiating circuit or operation of the electric-manual pull initiating circuit, and Zone 2 of the Releasing Panel must operate via the Low Air Pressure Alarm Switch upon loss of air pressure from the sprinkler system piping, due to operation of one or more sprinklers. The Double Interlock Preaction System will automatically actuate only when both Zone 1 and Zone 2 of the Releasing Panel have operated, energizing the Solenoid Valve.
This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
System actuation is carried out by Wet Pilot Line, consisting of Wet Pilot Sprinklers for detection. Actuation of Wet Pilot Line releases Deluge Valve, which allows water to flow into sprinkler line.
This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
System actuation is carried out by Dry Pilot Actuator, consisting of Dry Pilot Sprinklers for detection. Actuation of Dry Pilot Actuator releases Deluge Valve, which allows water to flow into sprinkler line. The Dry Pilot Sprinkler line to be pressurized with 42 psi (2.94 bar) air pressure.
Two independent Pressure Maintenance Devices are to be utilized for maintaining the supervisory air pressure and Dry Pilot line pressure.
This system utilizes a Deluge Valve Model ES0201 and Riser Check Valve Model CH. The Riser Check Valve isolates the Deluge Valve from the system air pressure. Riser Check Valve provides an air check so that the system can be automatically pressurized with a supervisory air or nitrogen pressure of 18 psi (1.26 bar). A supervisory low pressure alarm switch can be set at 6 psi (0.42 bar), on decreasing pressure, to indicate whether there are any abnormal leaks in the sprinkler system piping. Loss of air pressure from the system due to accidental leakage will not cause Deluge Valve to open.
System actuation is carried out by supplemental detection system, which typically comprises of 24 VDC heat detectors, smoke detectors, manual pull stations, etc. Actuation of the detection system automatically operates the Deluge Valve, allowing water to flow into the sprinkler piping system, to be discharged from any sprinklers that are open.
The Pre-Pack Cabinet and all interconnecting piping must be located indoors in a readily visible and accessible location and in an area having minimum temperature of 4oC (40oF). Heat tracing is not permitted. The automatic sprinklers, releasing devices, fire detection devices, must be UL Listed.
Two separate power supply connections to be provided to compressor and electric panel. Two separate terminal sets are provided in the Pre-Pack system.
Electric panel is to be powered by 230V AC, 50 Hz stabilized power supply (with surge protection).
The compressor power requirement is single phase 230V AC, 50 Hz (may vary in different countries) stabilized power supply (with surge protection).
As required by NFPA13, Fire Sprinkler System must be hydrotested and pressure need to be maintained without loss, for two hours. The test pressure shall be as per NFPA 13. In addition to the hydrostatic testing, dry pipe and double interlock pre-action system requires an additional low pressure air test.
Inspection and testing is to be carried out only by authorized and trained personnel. DO NOT TURN OFF the water supply or close any valve to make repair(s) or test the valve, without placing a roving fire patrol in the area covered by the system. Also inform the local security personal and central alarm station, so that there is no false alarm signal. It is recommended to carry out physical inspection of the system at least twice a week. The inspection should verify that no damage has taken place to any components and check for following normal condition of the system.
Inspection, Testing and Maintenance must be performed in accordance with NFPA and or authority having jurisdiction.
1 | BASE FRAME |
2 | CABINET |
3 | BUTTERFLY VALVE WITH TAMPER SWITCH |
4 | DELUGE VALVE |
5 | CHECK VALVE |
6 | PRESSURE GAUGE |
7 | ANTI RESET VALVE |
8 | DRY PILOT ACTUATOR |
9 | EMERGENCY RELEASE STATION |
10 | ANGLE VALVE |
11 | PRIMING VALVE |
12 | RESTRICTED CHECK VALVE |
13 | TRIM FITTINGS |
14 | PRESSURE SWITCH |
15 | SOLENOID VALVE |
16 | SPLASH PROOF FUNNEL |
17 | SPRINKLER ALARM |
18 | RELEASE PANEL |
AIR COMPRESSOR | RESTRICTED CHECK VALVE |
20 | JUNCTION BOX |
Friction loss expressed in equivalent length of Schedule 40 pipe and based on Hazen-Williams Formula with C=120 and a flowing velocity of 4.6 mtrs. (15 ft/sec) is as under. The friction loss is with Deluge Valve, Check Valve, Supply Manifold and System Shutoff Valve.
Valve Size | Equivalent Length in metres |
---|---|
50 mm (2”) | BASE FRAME |
80 mm (3”) | 17.5 |
100 mm (4”) | 20.0 |
150 mm (6”) | 46.2 |
200 mm (8”) | 72.0 |
Valve Size | Outer Diameter | Groove Diameter | Groove Width | Outlet face to Groove |
---|---|---|---|---|
50mm (2”) | 60mm (2.357”) | 57mm (2.250”) | 8mm (5/16”) | 16mm (5/8”) |
80mm (3”) | 89mm (3.5”) | 85mm (3.344”) | 8mm (5/16”) | 16mm (5/8”) |
100mm (4”) | 114mm (4.5”) | 110mm (4.334”) | 10mm (3/8”) | 16mm (5/8”) |
150mm (6”) | 165mm (6.496”)* | 161mm (6.385”) | 10mm (3/8”) | 16mm (5/8”) |
200mm (8”) | 219mm (8.625”) | 214mm (8.441”) | 11mm (7/16”) | 19mm (3/4”) |
*Pipe diameter 168(6.625”) is optional.
No | Description | Make | Approval | Datasheet |
---|---|---|---|---|
1 | Deluge Valve | EUROSAFE | UL Listed | |
2 | Check Valve | EUROSAFE | UL Listed with Pre-action system | |
3 | Single Interlock, Electric Actuation | EUROSAFE | UL Listed | |
4 | Single Interlock, Dry Pilot Actuation | EUROSAFE | UL Listed | |
5 | Single Interlock, Wet Pilot Actuation | EUROSAFE | UL Listed | |
6 | Double Interlock, Electric /Pneumatic Actuation | EUROSAFE | UL Listed | |
7 | Double Interlock, Electric /Electric Actuation | EUROSAFE | UL Listed | |
8 | Release Panel | Potter | UL Listed | |
9 | Pressure Alarm Switch | Potter | UL Listed | |
10 | Pressure Alarm Switch | Potter | UL Listed | |
11 | Butterfly Valve (System Shutoff Valve) | EUROSAFE | UL Listed | |
12 | Automatic Supervisory Air Supply (Compressor) | General Air Products | CE or UL Listed | |
13 | Air Pressure Maintenance Device | EUROSAFE | UL Listed with Pre-action System | |
14 | Nitrogen Maintenance Device | EUROSAFE |
Battery of 12V-14 Ah is standard supply in separate packing, it needs to be mounted in panel while installing the Pre-Pack . Higher capacity battery is optional supply.
SIZE | A | B | C | D | E | F | G | H | J | K | L | M | M1 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
50 NB | 800 | 152 | 248 | 248 | 690 | 407.5 | 171 | 185 | 275 | 800.5 | 86 | 1785 | 1325 |
80 NB | 800 | 152 | 248 | 248 | 690 | 407.5 | 171 | 185 | 275 | 800.5 | 86 | 1785 | 1325 |
100 NB | 870 | 90 | 345 | 345 | 730 | 420 | 187 | 185 | 275 | 937 | 86 | 1895 | 1400 |
150 NB | 930 | 80 | 385 | 385 | 750 | 420 | 215 | 190 | 315 | 1061 | 86 | 2035 | 1540 |
200 NB | 930 | 80 | 385 | 385 | 850 | 476 | 259 | 190 | 340 | 1170 | 86 | 2275 | 1770 |